Controlled switching of high voltage shunt reactor
This thesis characterized models and investigations into switching transient phenomena related to the shunt reactors and for reactive power control in the transmission system. Reactor banks play an important role in mitigating the voltage rise, otherwise known as Ferranti effect, which is characteri...
Saved in:
Main Author: | |
---|---|
Format: | Thesis |
Language: | English |
Subjects: | |
Online Access: | http://dspace.unimap.edu.my:80/xmlui/bitstream/123456789/44119/1/p.1-24.pdf http://dspace.unimap.edu.my:80/xmlui/bitstream/123456789/44119/2/full%20text.pdf |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
id |
my-unimap-44119 |
---|---|
record_format |
uketd_dc |
spelling |
my-unimap-441192016-11-22T06:48:08Z Controlled switching of high voltage shunt reactor Mazyed Awan Ahmed, Al-Tak This thesis characterized models and investigations into switching transient phenomena related to the shunt reactors and for reactive power control in the transmission system. Reactor banks play an important role in mitigating the voltage rise, otherwise known as Ferranti effect, which is characteristic to long lightly loaded transmission lines having high capacitive charging current. The energizing and de-energizing of the reactor bank introduces high frequency transients that might stress the insulation of the switching equipment leading to equipment failures. The work presents different phenomena associated with reactor bank de-energisation and addresses the issue of circuit breaker application when interrupting low inductive currents from an engineering stand point. The work illustrates a case study simulated in the Alternative Transients Program part of the Electromagnetic Transients Program package (ATP\EMTP) to demonstrate current chopping and re-ignition phenomenon associated with reactor bank switching. Mitigation methods for the aforementioned issues are also evaluated. This work focus on finding the transient overvoltages in case of single and three phase’s system and determine the ideal switching case that gives the lowest overvoltage magnitude at the shunt reactor components. Also in this study, varying opening times of circuit breaker for three-phase connections were used to determine the stress of shunt reactor components. We can stimulate the synchronous switching state of the shunt reactor by variation in the circuit breaker times. First, in case of the single-phase analysis, Laplace transform were used to calculate the transient overvoltages, while ATP simulation for validation were used to compare the acquired results. In order to reproduce the switching operation of shunt reactor, the Alternative Transient Program (ATP/EMTP) was applied. The reason ATP was applied here is because it gives solution in time domain and very helpful in the comparisons with analytical method conducted. On the other hand, in case of the three- phase shunt reactor, the de-energisation of the shunt reactor was used to identify the transient overvoltages for synchronous switching. The first method applied in this study are uncontrolled switching that depend on opening the circuit breaker at one time for all phases, while the second method is controlled switching, in other words, to give the circuit breaker limited time for each phase, the opening time is based on the value of the current across the circuit breaker that allows the lowest transient overvoltage. The final method applied in this work is the surge arrester for the protection and minimize the transient overvoltages. Universiti Malaysia Perlis (UniMAP) 2014 Thesis en http://dspace.unimap.edu.my:80/xmlui/handle/123456789/44119 http://dspace.unimap.edu.my:80/xmlui/bitstream/123456789/44119/1/p.1-24.pdf c47cd198635dc65bfe0957003fd5a2fa http://dspace.unimap.edu.my:80/xmlui/bitstream/123456789/44119/2/full%20text.pdf 53a0491f86ba74b87b65bcaa959c6cc3 http://dspace.unimap.edu.my:80/xmlui/bitstream/123456789/44119/3/license.txt 8a4605be74aa9ea9d79846c1fba20a33 High voltage shunt reactor Reactive power control Shunt reactor Transmission system Controlled switching School of Electrical Systems Engineering |
institution |
Universiti Malaysia Perlis |
collection |
UniMAP Institutional Repository |
language |
English |
topic |
High voltage shunt reactor Reactive power control Shunt reactor Transmission system Controlled switching |
spellingShingle |
High voltage shunt reactor Reactive power control Shunt reactor Transmission system Controlled switching Mazyed Awan Ahmed, Al-Tak Controlled switching of high voltage shunt reactor |
description |
This thesis characterized models and investigations into switching transient phenomena related to the shunt reactors and for reactive power control in the transmission system. Reactor banks play an important role in mitigating the voltage rise, otherwise known as Ferranti effect, which is characteristic to long lightly loaded transmission lines having
high capacitive charging current. The energizing and de-energizing of the reactor bank introduces high frequency transients that might stress the insulation of the switching equipment leading to equipment failures. The work presents different phenomena associated with reactor bank de-energisation and addresses the issue of circuit breaker application when interrupting low inductive currents from an engineering stand point.
The work illustrates a case study simulated in the Alternative Transients Program part
of the Electromagnetic Transients Program package (ATP\EMTP) to demonstrate
current chopping and re-ignition phenomenon associated with reactor bank switching.
Mitigation methods for the aforementioned issues are also evaluated. This work focus
on finding the transient overvoltages in case of single and three phase’s system and
determine the ideal switching case that gives the lowest overvoltage magnitude at the
shunt reactor components. Also in this study, varying opening times of circuit breaker
for three-phase connections were used to determine the stress of shunt reactor
components. We can stimulate the synchronous switching state of the shunt reactor by
variation in the circuit breaker times. First, in case of the single-phase analysis, Laplace
transform were used to calculate the transient overvoltages, while ATP simulation for
validation were used to compare the acquired results. In order to reproduce the
switching operation of shunt reactor, the Alternative Transient Program (ATP/EMTP)
was applied. The reason ATP was applied here is because it gives solution in time
domain and very helpful in the comparisons with analytical method conducted. On the
other hand, in case of the three- phase shunt reactor, the de-energisation of the shunt
reactor was used to identify the transient overvoltages for synchronous switching. The
first method applied in this study are uncontrolled switching that depend on opening the
circuit breaker at one time for all phases, while the second method is controlled
switching, in other words, to give the circuit breaker limited time for each phase, the
opening time is based on the value of the current across the circuit breaker that allows
the lowest transient overvoltage. The final method applied in this work is the surge
arrester for the protection and minimize the transient overvoltages. |
format |
Thesis |
author |
Mazyed Awan Ahmed, Al-Tak |
author_facet |
Mazyed Awan Ahmed, Al-Tak |
author_sort |
Mazyed Awan Ahmed, Al-Tak |
title |
Controlled switching of high voltage shunt reactor |
title_short |
Controlled switching of high voltage shunt reactor |
title_full |
Controlled switching of high voltage shunt reactor |
title_fullStr |
Controlled switching of high voltage shunt reactor |
title_full_unstemmed |
Controlled switching of high voltage shunt reactor |
title_sort |
controlled switching of high voltage shunt reactor |
granting_institution |
Universiti Malaysia Perlis (UniMAP) |
granting_department |
School of Electrical Systems Engineering |
url |
http://dspace.unimap.edu.my:80/xmlui/bitstream/123456789/44119/1/p.1-24.pdf http://dspace.unimap.edu.my:80/xmlui/bitstream/123456789/44119/2/full%20text.pdf |
_version_ |
1747836823710728192 |